LT3000SERIES compact Hardware Specifications
Functional Specifications
| Model |
LT3300-S1-D24 |
LT3300-L1-D24 |
LT3301-L1-D24 |
| Display Type |
STN Color LCD |
Monochrome LCD |
| Display Colors |
4,096 Colors |
Black and White (16 Shades) |
| Backlight |
White LED (When the backlight needs to be replaced , please contact your local distributor.) |
| Display Resolution |
W320 x H240pixels |
| Effective Display Area |
W117.2mm x H88.4mm |
| Memory |
Application |
6MB FLASH EPROM *1 |
| Data Backup |
SRAM 128KB *2 |
Touch Panel |
Type |
Resistive Film (analog) |
| Resolution |
1024 x 1024 |
Control Memory |
Variable Area |
64KB SRAM (uses lithium battery) *2 |
| Program Area |
132KB FLASH EPROM (enough for 15,000 program steps) *3 |
| Number of Step |
15,000 steps *4 |
| Interface |
Ethernet |
IEEE802.3u,10BASE-T/100BASE-TX |
£ |
| Serial |
COM1: RS232C/RS422/RS485 Asynchronous Transmission / Data Length: 7 bit/8 bit Parity: none, Odd or Even Stop Bit: 1bit/2bit Data transmission Speed: 2400bps to 115.2Kbps Connector: DSUB-9pin plug |
| USB |
USB1.1 Host I/F x 1, USB TYPE-A connector |
| Control(DIO) |
DIO (NPN Type) (Model:LT330¡ö-¡ö1-D24-K) |
NPN / PNP Input: 16 points, NPN Output: 16 points Connector: 38 pins |
DIO (PNP Type) (Model:LT330¡ö-¡ö1-D24-C) |
NPN / PNP Input: 16 points, PNP Output: 16 points Connector: 38 pins |
| EX Module (EXT1) |
To mount EX Module *5 |
| AUX / Expansion Unit (EXT2) |
To mount CANopen Master Unit *5 |
- *1
- It is user active capacity.
- *2
- Service life of lithium batteries is 10 years or more at a battery ambient temperature of 40oC or less , 4.1 years or more at 50oC or less, and 1.5 years at 60oC or less. The backup period is about 100 days after the initial charge (fully charged), and about 6 days up to the end of battery life.
- *3
- Using Pro-face's calculation method
- *4
- Up to 60,000 steps can be made, but this reduces the capacity of the internal screen data memory by 1MB.
- *5
- EX Module and CANopen Master Unit cannot be used at the same time.
LT3000SERIES compact EX Module / CANopen Master Unit Specification
With the EX module I/F, 3 sets (5.7inch) or 2 sets(3.8inch) of 13 Types of EX modules can be added on. That enables a high degree of customization, more than 100 combinations, for a diversity of needs and future expansions.
EX Module / CANopen Master Unit Specification
External view and sizes of various parts (mm)
| |
A |
B |
C |
D |
E |
F |
G |
| EXM-DDl8DT |
3.8 |
23.5 |
90 |
4.5 *1 |
14.6 |
70 |
- |
| EXM-DDl16DT |
| EXM-DRA8RT |
| EXM-DRA16RT |
| EXM-DDO8UT |
| EXM-DDO8TT |
| EXM-DMM8DRT |
| EXM-AMl2HT |
| EXM-ALM3LT |
| EXM-AMM3HT |
| EXM-AMO1HT |
| EXM-DDO16UK |
17.6 |
11.3 |
| EXM-DDO16TK |
| CA8-CANLT-01 |
5.5 |
23.5 |
4.5 |
£ *2 |
71 |
6*3 |
- *1 The length of the pulled out hook is 8.5mm.
- *2 CANopen Master Unit Interface is at the bottom of the unit.
-
- *3 Length of the hooks when pulled out is 12.1mm.
Using the LT unit as a master, you can communicate over a CANopen network.
CANopen Master Unit
| Product Name |
CANopen Master Unit |
Using the LT unit as a master, you can communicate over a CANopen network. |
| Model No. |
CA8-CANLT-01 |


| CA8-CANLT-01 |
| Communication Type |
1:N |
| Connection Method |
Multi-drop connection |
| Communication Method |
CSMA/NBA, half-duplex serial communication |
Transfer Speed / Communication Distance |
Baud Rate |
1,000kbps |
800kbps |
500kbps |
250kbps (Factory Settings) |
125kbps |
50kbps |
| |
Bus Length |
20m |
40m |
100m |
250m |
500m |
1000m |
| Number of Stations |
Max.63 stations, Bit variable input: 256, Bit variable output: 256, Integer variable input: 64, Integer variable output: 64 |
| Connection Shape |
D-Sub 9-pin plug |
| Status LED |
PWR (green) ON: The power turns ON, OFF: The light is OFF¡¡ RUN (green): The light is ON or blinks when communication is enabled. ERR(Red): The light is ON or blink when the connected slave has an error. |
| Power Consumption |
2.4W or less |
| Weigvht |
500g or less |
CANopen Pin Connections
| Pin Connection |
|
Signal Name |
Description |
 |
1 |
£ |
|
| 2 |
CAN_L |
CAN_L Bus Line |
| 3 |
CAN_GND |
CAN Ground |
| 4 |
£ |
|
| 5 |
£ |
|
| 6 |
£ |
|
| 7 |
CAN_H |
CAN_H Bus Line |
| 8 |
£ |
|
| 9 |
£ |
|
External Dimensions
|
A |
B |
C |
D |
E |
F |
G |
| CA8-CANLT-01 |
5.5 |
23.5 |
90 |
4.5 |
£¡ù3 |
71 |
6¡ù4 |
 |
- ¡ù3 CANopen Master Unit Interface is at the bottom of the unit.